Rated Doors
The rated door at the boiler room does not close due to binding on the floor. Recommend replacement of door, and hardware only. Existing rated frame to remain.
Rescue Windows
Rescue windows must provide an unobstructed opening of at least 6 sf with no dimension less than 24 inches. The rescue window from Room 420 is 19" wide. Replace window with casement window that meets 24" clear space requirement.
Pavement Markings
Provide painted crosswalks at south end of main parking area.
Stripping is worn and in need of repainting.
Toilet Rooms
Toilet rooms for kindergarten and primary grades should if possible be placed adjacent to these rooms. All the existing rooms have a toilet room located within them. Recommend that the District renovate 3 toilet rooms to provide full accessibility.
Kitchen
Replace outdated grease trap in kitchen with a more modern and effective unit to guard against drain line stoppages.
Area of Assembly Exiting
Libraries although not technically places of assembly (unless size is over 1,000 sf), should incorporate place of assembly safety standards because of the potential for high occupancy. Includes replacing double door entrance with inset double door entrance that swings in the direction of egress. Also placement of panic hardware on each leaf, and installation of lighted exit sign.
Barry
Elementary
Junior/Senior
High School
Parker
Elementary
Randall
Elementary
Smith
Elementary
Virgil
Elementary
Kaufman Ctr.
Bus Garage
District
Wide
Maintenance Building/Loading Dock
Remove and replace deteriorated loading dock retaining wall. Provide new guardrail.
Athletic Fields
Provide irrigation/water cannons for the athletic fields
Wood Overhead Door
The wood overhead door to access the gym storage that is used as an office is not a suitable exit. Replace door with 1 set of double doors.